Eight degrees sits in an awkward band. It is too large to be a new thermocouple's tolerance — Type K standard limits are ±2.2 °C or 0.75 % of reading, which at 600 °C is 4.5 °C — and too small for developed green rot, which is documented at tens of degrees. That band points at three suspects: the cold junction, anything in the loop that is not Type K alloy, and chromium depletion in the positive leg. Check them in that order, because the first costs nothing and the third is the only one you cannot undo.

The cold junction adds its error one for one

Cold-junction compensation is the one error term that transfers at a ratio of exactly 1:1. If the CJC sensor believes the terminals are 8 °C warmer than they are, every channel on that block reads 8 °C low, with no relation to the process or the probe. An 8 °C error therefore does not require an 8 °C probe fault; it requires an 8 °C error at the terminals, which is a plausible consequence of a cabinet that gained a heat source, a fan that stopped, or a terminal block that is no longer isothermal.

It is also the cheapest thing to test: put an independent thermometer against the terminal block, read the CJC value the instrument reports, and compare the two. If they disagree by the size of your error, no amount of probe replacement will change the number.

Anything in the loop that is not Type K creates a junction

A copper splice, a terminal strip, a wrong-alloy connector, or extension cable of the compensating rather than extension grade all insert a junction the instrument is not compensating. The error scales with the temperature difference across that junction, so a splice in a warm cabinet costs more than the same splice in still air. Six months is precisely the timescale on which a terminal screw loosens or a splice oxidises.

Polarity belongs here too. A fully reversed pair would not read a steady 8 °C low, but one reversed extension section inside an otherwise correct loop produces a fixed offset that is easy to mistake for drift.

Chromium depletion reads low, and it is permanent

Green rot is the classic Type K failure. In a low-oxygen atmosphere between roughly 800 and 1100 °C, chromium is selectively oxidised out of the positive leg, the thermoelectric voltage falls, and the reading drifts negative — tens of degrees, sometimes 50 °C or more, with the wire becoming brittle enough to break. The negative leg is not affected. The name comes from the greenish cast on the chromel, and a field check follows from it: chromel is normally non-magnetic, so a positive leg that now responds to a magnet is a strong indicator.

The temperature window matters. If your process runs at 400 °C, green rot is not your mechanism and you should stop looking for it. Hydrogen, cracked ammonia, stagnant protection tubes and cyclic oxidising-reducing service are the conditions that bring it on, which is why heat-treat and annealing furnaces are where it shows up.

The 250–550 °C band explains two or three degrees, not eight

Separate from green rot, Type K undergoes short-range atomic ordering between about 250 and 550 °C that shifts the EMF by 1 to 3 °C, reaching around 5 °C in heavily cycled wire. Unlike green rot this is reversible: cycling above 600 °C or cooling below 250 °C restores the output. It shows up as hysteresis between a rising and a falling cycle, not as a permanent offset. It can contribute to your 8 °C, but it cannot be the whole of it.

How to split the three in one shift

  • Compare the reported CJC temperature with an independent thermometer at the terminals. One for one, so any match is the answer.
  • Walk the loop looking for copper: splices, terminal blocks, wrong-grade extension, wrong connectors. Every one of them is an uncompensated junction.
  • Substitute a calibrated assembly at the same immersion depth. If the error follows the electronics, it was never the wire.
  • Once at temperature, cycle the process above 600 °C and back. An error that disappears was ordering, not damage.
  • Pull the element and look at the positive leg: green cast, brittle, magnetic. All three together means replacement, not recalibration.
The honest split

A thermocouple that has drifted 8 °C low cannot be diagnosed from the reading alone, and a lab calibration of the removed element will not settle it either, because inhomogeneity along the wire means a bench calibration no longer represents the installed gradient. Split the loop physically — electronics first, then wiring, then the element — and only then decide whether to recalibrate or replace.

When the reading is not drift at all

Three configuration faults look exactly like drift: the instrument linearising the wrong thermocouple type, a CJC fixed at a manual value rather than measured, and insufficient immersion for the junction to reach process temperature, where a common rule of thumb is ten sheath diameters. None is the wire's fault, and all three are cheaper to check than a replacement element.

If the process genuinely sits at 800–1100 °C with limited oxygen, the durable fix is not a better Type K. Type N was designed against these mechanisms, since its higher chromium and silicon content forms a protective oxide that resists depletion, and it suppresses ordering too. Above about 1100 °C the answer is a noble-metal type.

Questions we get asked
Can a Type K thermocouple drift 8 °C low in six months?
Yes, but only through the wire or the cold junction. Cold-junction error transfers one for one, so an 8 °C terminal error gives an 8 °C reading error. Chromium depletion in the positive leg also drifts negative, though usually by tens of degrees, and only above roughly 800 °C in low-oxygen service.
How do I check whether green rot is the cause?
Look at the positive leg. Green rot leaves a greenish cast, makes the wire brittle, and makes chromel magnetic, which it normally is not. It also only appears in low-oxygen atmospheres between about 800 and 1100 °C. If the process runs cooler than that, the mechanism is not available and the error is elsewhere.
Is an 8 °C error within Type K tolerance?
No. Standard limits of error for Type K are ±2.2 °C or ±0.75 % of reading, whichever is greater, so at 600 °C the allowance is 4.5 °C. Special-limits wire is ±1.1 °C or ±0.4 %. An 8 °C deviation at that temperature is outside both and indicates a real fault.
Should I recalibrate the drifted thermocouple or replace it?
Replace it if the positive leg shows green rot or brittleness, because the composition has changed along the wire and a bench calibration will not match the installed gradient. Recalibration is reasonable only when the error came from the cold junction or the loop wiring, which are corrected rather than compensated.
Citable facts
Sources

Send the specification — diameter, grade, temper, quantity.

We come back with a confirmed lead time and the documentation we can issue for the shipment. 100 g sample at cost; orders from 1 kg.